Megger MIT220 250/500 V Insulation and continuity tester with Digital/Analog display

Category: Megger
  • 250/500V Insulation Test Voltage Range
  • Insulation testing to 1000 MΩ
  • Continuity testing at 200 mA down to 0.01 Ω
  • Live circuit warning (voltage display) and test inhibit
  • Digital/Analog display
  • Meets the international EN61557 requirements of the rated test voltage into a 1 mA load
  • Digital display of insulation measurement up to 1000 MΩ on a logarithmic Analog arc and a digital display
  • Continuity range has 0.01 resolution and a short circuit current in excess of 200 mA
  • Automatic continuity testing leaves both hands free. No need to press the test button
  • Automatic power-off if left unattended reduced wasted battery life
  • Automatic voltage detection avoids accidental contact with live circuits
  • Test lead zero allows compensation for test lead resistance
  • Buzzer range operates at <2 Ω
  • Alkaline or rechargeable batteries
  • –10°C to +55°C operating temperature
  • CAT III 600 V
  • Conforms to EN61557-1

    The Megger MIT220 250/500 V Insulation and continuity tester is one of the smallest insulation testers available on the market today. With options of one, two and three voltage test voltage instruments, the Megger MIT220 instruments offer a range of safety and operation features.

    The display of the Megger MIT220 offers a combination of digital readout and analog display, using Megger’s patented DART display technology, which includes the benefits of an LCD display, such as robust, clear and accurate measurement, with an analog pointer response for evaluating circuit charge and discharge characteristics.

    The Megger MIT 220 housing is in tough ABS, designed to with-stand the rigorous of hard use, and is small enough to drop into your pocket when not in use. Battery requirements are 6 AA batteries of either standard alkaline or nickel metal hydride (NiMH) rechargeable type.

    Continuity testing
    Automatic continuity testing is performed at 200 mA to ensure compliance with international requirements. There is no need to press the test button.

    The Megger MIT-220 will measure up to 100 Ω on continuity, of which 0-10 Ω is performed at greater than 200 mA to meet international electrical testing requirements. Lead null is possible up to 9.99 Ω of test lead resistance,ensuring the ability to null fused test leads as well as standard leads.

    Continuity buzzer
    A continuity buzzer provides a means of rapid cable testing and circuit identification, with voltage protection should you accidentally touch a live circuit. The buzzer operates at a 2 Ω threshold. The buzzer operates at a 2 Ω threshold.

    Insulation testing
    Insulation testing is possible up to 1000 Ω on all ranges. Auto discharge ensures all circuits are safely discharged after testing. 1000 V insulation test ranges have a high voltage warning prior to test voltage being applied.

    Safety
    The Megger MIT220 Insulation and continuity tester is designed with safety as its primary objective. The Megger MIT/200 meets or exceed the requirements of safety directive IEC 61010 and EN61557 for insulation and continuity testing.

    Default fault meter
    A built-in voltmeter automatically switches in when the instrument is connected to a circuit with an AC or DC voltage greater than 25 V.

    Insulation Test inhibit
    Circuits in excess of 25 V will generate a voltage warning. Circuits over 50 V will inhibit testing of the insulation, protecting the operator and the Megger MIT220 from injury or damage.

    600V CAT III
    The Megger MIT220 Insulation and continuity tester has been designed for use on applications up to 600 V CAT III.

    Applications
    The Megger MIT-220 Insulation/continuity tester will find applications in electrical contracting, both on domestic and industrial systems, as well as site maintenance and service departments. The Megger MIT220 of insulation and continuity testers are ideal for testing transformers, motors, generators switch gear, panel building, domestic appliances, power tools etc., as well as fixed electrical wiring systems.

    The Megger MIT-220's small size and light weight make the Megger MIT220 ideal for those engineers that need to carry them for extended periods. All instruments meet the requirements of most International Standards including VDE0413 Part 1 and BS7671 (the 16th Edition of the IEE Wiring Regulations).

    Specifications
    Insulation testing 250 V
    500 V
    1000 MΩ range
    Auto-ranging
    Auto discharge
    Test inhibit
    Live circuit voltage display
    Continuity testing Continuity @ >200 mA
    Continuity to 0.01 Ω
    Test lead null (9.99 Ω)
    Automatic continuity test
    Continuity buzzer with 2 Ω threshold
    Default volts warning
    Measuring range Ranges 10 kΩ-1000 MΩ on all ranges
    Terminal voltage on open circuit (d.c.): -0% +25% of rated voltage
    Short circuit current: 205 mA +10 mA –5 mA
    Test current on load: >1 mA at minimum pass values of insulation as specified inBS7671, HD384, IEC364 and VDE0413 part 1
    Accuracy (at 20°C) ±3% of reading
    ±2 digits up to 10 MΩ
    ±5% of reading ±2 digits up to 100 MΩ
    ±30% of reading up to 1000 MΩ
    Continuity ranges Measuring range: 0.01Ω-100 Ω(0 -550Ω on Analog scale)
    Open circuit voltage: 5V±1 V
    Short circuit current: 205 mA, ±5 mA (0-10 Ω)>20 mA (0 - 100 Ω)Ω
    Accuracy (at 20°C) ±0,01 Ω to 9,99 Ω ±3% ±2 digits
    10,0 Ω to 99,9 Ω ±5% ±2 digits
    Zero offset adjust: 0 to 9,99 Ω
    Continuity buzzer Operates at <2 Ω
    Default voltmeter >25 V AC or dc. is applied display will operate as a voltmeter.
    Test inhibit Range: 25 V to 600 V @ 50/60 Hz & dc
    Accuracy: 25V to 450 V AC/dc ±1% ± 1 digit
    450V to 600V AC ±2% ±1 digit
    Auto power down Auto power down operates after 10 minutes if left in standby mode.
    Environmental Operation temperature
    Temperature and humidity
    -10°C to +55°C (14°F to 130°F)
    Operating humidity: 93% R.H. at +40°C max. (93% R.H. at 104°F)
    Storage temperature -20°C to +65°C (-13°F to 150°F)
    IP rating IP40
    Fuses Terminals 500 mA (F) 600 V, 32 x 6 mm Ceramic HBC 50 kA minimum.
    Display shows if fuse is ruptured.
    Safety Meets the requirements of EN61010-1 Cat III 600V phase to earth.
    Automatic discharge After an insulation test the item under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored.
    Power supply Battery 6 x 1,5 V cells IEC LR6 type (AA alkaline).
    Rechargeable NiMH cells may be used.
    Battery condition is constantly shown on the display as a four-section bar-graph.
    Battery life 3000 consecutive tests (5 seconds per test) on any test using 2Ahbatteries.
    Weight 550gms approx. (1.2lbs)
    Dimensions 7.7 x 3.9 x 1.6 inches (195 x 98 x 40mm)
    E.M.C In accordance with IEC61326-1